Cart()
 
 
Categories
Contact Us
  • A&S Power Supply Co.,Ltd
  • Address:469, Xinsheng Road, Gaoxin District, Chengdu, Sichuan, China
  • Tel:+86-28-65376776
  • Fax:+86-28-86129221
  • Email:inverter@electrical8.com
  • Contact Person:Karina
Home / Products / power supply / Omron Power Supply / S8VS / Omron Power Supply S8VS Series S8VS-24024AP

Omron Power Supply S8VS Series S8VS-24024AP

Omron Power Supply S8VS Series S8VS-24024AP
share

Maintenance Forecast Monitor Type , Input 100 to 240 VAC , 240 W , Output 24 V 10 A , With Undervoltage Alarm (Ttransistor (Sourcing))
Power rating 240 W
Efficiency 85% TYP. ï¼ˆAt 100 VAC input)88% TYP. ï¼ˆAt 200 VAC input)
Rated input voltage 100 to 240 VAC
Allowable-input voltage variable range 85 to 264 VAC80 to 370 VDC
Note at DC input The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Frequency 50/60 Hz (47 to 63 Hz Single-phase)
Rated input current 2.9 A TYP. ï¼ˆAt 100 VAC input)1.5 A TYP. ï¼ˆAt 200 VAC input)
Power factor 0.9 Min.
Harmonic Current EN61000-3-2
Leakage current 0.5 mA Max. (At 100 VAC input)1.0 mA Max. (At 200 VAC input)
Inrush current 14 A TYP. ï¼ˆAt 100 VAC input (For cold start at 25 CEL))28 A TYP. ï¼ˆAt 200 VAC input (For cold start at 25 CEL))
Rated output voltage 24 VDC
Output voltage variable range -10 to +15% (With V. ADJ)(The output voltage may increase beyond the allowable voltage range (up to +15% of the rated voltage) depending on the operation of the output voltage adjuster (V.ADJ). When adjusting the output voltage, check the output voltage of the Power Supply and be sure that the load is not damaged.)
Ripple 2%(p-p) Max. (Under the rated I/O conditions.)160 mV Max. (Under the rated I/O conditions.)
Static input variation influence 0.5% Max. (At 85 to 264 VAC input, 100% load)
Static load variation influence 1.5% Max. (At rated input, 0 to 100% load)
Ambient temperature variation influence 0.05 %/CEL Max.
Rated output current 10 A
Start up time 510 ms TYP. ï¼ˆ100 VAC input)510 ms TYP. ï¼ˆ200 VAC input)
Hold time 46 ms TYP. ï¼ˆ100 VAC input)46 ms TYP. ï¼ˆ200 VAC input)
Overload protection 105% to 160% of the rated output currentInverted L voltage drop, Automatic reset
Overvoltage protection Operated at 130% Min. of the rated output voltage, Shut-offResetting: Reset the power by turning it back (OFF time: at least 3 min)
Overheat protection No
Output voltage indication Yes (Resolution: 0.1 V / Accuracy: +/- 2% (percentage of output voltage value) +/- 1 digit Max.)
Output current indication Yes (Resolution: 0.1 A / Accuracy: +/- 5% F.S. (percentage of rated output current value) +/- 1 digit Max.)
Peak-hold current indication Yes (Resolution: 0.1 A / Accuracy: +/- 5% F.S. (percentage of rated output current value) +/- 1 digit Max. / Minimum detectable signal width: 10 ms (20 ms Max.))
Maintenance forecast monitor indication Yes (Resolution: 0.5 year / Setting range: 0.0 to 5.0 years)
Maintenance forecast monitor output Yes (open collector output), 30 VDC Max., 50 mA Max., Sourcing (PNP)
Total run time monitor output No
Undervoltage alarm indication Yes (Resolution: 0.1 V / Setting range: 18.5 to 26.3 V)
Undervoltage alarm output Yes (open collector output), 30 VDC Max., 50 mA Max., Sourcing (PNP)
Power failure alarm output No
Parallel operation No (However, backup operation is possible; external diodes required.)
Series operation Yes (Up to 2 Power Supplies with external diode)
Remote sensing function No
Applicable standard (UL) Standard No.: UL Listed: UL508 (Listing), UL UR: UL60950-1 (Recognition)
Applicable standard (CSA) Standard No.: cUL: CSA C22.2 No.107.1, cUR: CSA C22.2 No.60950-1
Applicable standard (EN) Standard No.: EN50178, EN60950-1
Applicable standard (EC Directive (EMI)) Emission Enclosure: Conforms to EN61204-3 Class AEmission AC mains: Conforms to EN61204-3 Class A and based on FCC Class AEMS: EN61204-3 High severity levels
Applicable standard(VDE) Standard No.: VDE0160, VDE0805 Teil 1 File number:
Applicable standard(SEMI) F47-0200 (200 VAC input)
Applicable standard(Other) Other(s): KOSHA S Mark
Ambient temperature Operating: -10 to 60 CELStorage: -25 to 65 CEL(with no icing or condensation)
Ambient humidity Operating: 25 to 85%Storage: 25 to 90%(With no icing or condensation)
Dielectric strength Between all inputs and all outputs/alarm outputs: 3 kVAC for 1 min (Detection current: 20 mA)Between all inputs and PE terminals: 2 kVAC for 1 min (Detection current: 20 mA)Between all outputs/alarm outputs and all PE terminals: 1 kVAC for 1 min (Detection current: 20 mA)Between all outputs and all alarm outputs: 500 VAC for 1 min (Detection current: 20 mA)
Insulation resistance Between all outputs/alarm outputs and all inputs/PE terminals: 100 MOhm Min. (at 500 VDC)
Vibration resistance 10 to 55 Hz, 0.375 mm single amplitude in each 3 directions for 2 hours
Shock resistance 150 m/s**2, in each 6 directions 3 times
Output indicator Yes (color: green)
Heat radiation Natural air-cooling
Construction Covered type
Terminal type Screw terminal
Mounting type DIN Rail mounting type
Weight 1150 g Max.

Omron S8JX Switch Mode Power S8JX-P05024CD
Omron S8JX Switch Mode Power S8JX-P05024CD
Covered type , Input 100 to 240 VAC , 50W , Output 24V 2.1A , DIN Rail mounting typePower rating 50 WEfficiency 77% Min.Rated input voltage 100 to 240 VACAllowable-input&
Omron Power Supply S8VS Series S8VS-09024BE
Omron Power Supply S8VS Series S8VS-09024BE
Total Run Time Monitor , Input 100 to 240 VAC , 90 W , Output 24 V 3.75 APower rating 90 WEfficiency 83% TYP. ï¼ˆAt 100 VAC input)85% TYP. ï¼ˆAt 200 
Omron Power Supply S82S S82S-7705
Omron Power Supply S82S S82S-7705
Input 12 to 24 VDC , 7.5 W , Output 5 V 1.5 APower rating 7.5 WEfficiency 66% Min.Rated input voltage 12 to 24 VDCAllowable-input voltage variable range 10.2 to 27.6 
Omron Power Supply S8JX Switch Mode Power S8JX-P15012C
Omron Power Supply S8JX Switch Mode Power S8JX-P15012C
Covered type , Input 100 to 240 VAC , 150W , Output 12V 13A , Front-mounting typePower rating 150 WEfficiency 78% Min.Rated input voltage 100 to 240 VACAllowable-input voltage
Omron Power Supply S8JX Switch Mode Power S8JX-G10048C
Omron Power Supply S8JX Switch Mode Power S8JX-G10048C
Covered type , Input 100 to 240 VAC , 100 W , Output 48 V 2.1 A , Front-mounting typePower rating 100 WEfficiency 83% Min.Rated input voltage 100 to 240 VACAllowable
Omron Power Supply S8VS Series S8VS-06024A
Omron Power Supply S8VS Series S8VS-06024A
Maintenance Forecast Monitor Type , Input 100 to 240 VAC , 120 W , Output 24 V 5 A , With Undervoltage Alarm (Ttransistor (Sourcing))Power rating 120 WEfficiency 83% 
Omron Power Supply S8VM Series S8VM-05005CD
Omron Power Supply S8VM Series S8VM-05005CD
Standard Type , Covered Type , DIN Rail Mounting Bracket Type , Input 100 to 240 VAC , 50 W , Output 5 V 10 APower rating 50 WEfficiency 80% Min.Rated inpu
Omron Power Supply S8VS Series S8VS-09024-F
Omron Power Supply S8VS Series S8VS-09024-F
Maintenance Forecast Monitor Type , Input 100 to 240 VAC , 90 W , Output 24 V 3.75 APower rating 90 WEfficiency 83% TYP. ï¼ˆAt 100 VAC input)85% TYP. ï¼ˆAt&nbs
Omron Power Supply S8VS Series S8VS-18024B
Omron Power Supply S8VS Series S8VS-18024B
Total Run Time Monitor , Input 100 to 240 VAC , 180 W , Output 24 V 7.5 APower rating 180 WEfficiency 85% TYP. ï¼ˆAt 100 VAC input)87% TYP. ï¼ˆAt 200 
Omron Power Supply S8EX Series S8EX-P10005
Omron Power Supply S8EX Series S8EX-P10005
Open type , Input 100 to 240 VAC , 100W , Output 5V 20APower rating 100 WEfficiency 81% Min. ï¼ˆAt 100 VAC input)84% Min. ï¼ˆAt 200 VAC input)Rated inpu