Cart()
 
 
Categories
Contact Us
  • A&S Power Supply Co.,Ltd
  • Address:469, Xinsheng Road, Gaoxin District, Chengdu, Sichuan, China
  • Tel:+86-28-65376776
  • Fax:+86-28-86129221
  • Email:inverter@electrical8.com
  • Contact Person:Karina
Home / Products / power supply / Omron Power Supply / S8VS / Omron Power Supply S8VS Series S8VS-48024B

Omron Power Supply S8VS Series S8VS-48024B

Omron Power Supply S8VS Series S8VS-48024B
share

Total Run TimeMonitor , Input 100 to 240 VAC , 480 W , Output 24 V 20 A
Power rating 480 W
Efficiency 85% TYP. ï¼ˆAt 100 VAC input)89% TYP. ï¼ˆAt 200 VAC input)
Rated input voltage 100 to 240 VAC
Allowable-input voltage variable range 85 to 264 VAC80 to 370 VDC
Note at DC input The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Frequency 50/60 Hz (47 to 63 Hz Single-phase)
Rated input current 5.8 A TYP. ï¼ˆAt 100 VAC input)2.8 A TYP. ï¼ˆAt 200 VAC input)
Power factor 0.95 Min.
Harmonic Current EN61000-3-2
Leakage current 0.5 mA Max. (At 100 VAC input)1.0 mA Max. (At 200 VAC input)
Inrush current 14 A TYP. ï¼ˆAt 100 VAC input (For cold start at 25 CEL))28 A TYP. ï¼ˆAt 200 VAC input (For cold start at 25 CEL))
Rated output voltage 24 VDC
Output voltage variable range -10 to +15% (With V. ADJ)(The output voltage may increase beyond the allowable voltage range (up to +15% of the rated voltage) depending on the operation of the output voltage adjuster (V.ADJ). When adjusting the output voltage, check the output voltage of the Power Supply and be sure that the load is not damaged.)
Ripple 2%(p-p) Max. (Under the rated I/O conditions.)310 mV Max. (Under the rated I/O conditions.)
Static input variation influence 0.5% Max. (At 85 to 264 VAC input, 100% load)
Static load variation influence 1.5% Max. (At rated input, 0 to 100% load)
Ambient temperature variation influence 0.05 %/CEL Max.
Rated output current 20 A , 30 A (Peak current at 200 VAC)
Start up time 460 ms TYP. ï¼ˆ100 VAC input)340 ms TYP. ï¼ˆ200 VAC input)
Hold time 37 ms TYP. ï¼ˆ100 VAC input)41 ms TYP. ï¼ˆ200 VAC input)
Overload protection 105% to 160% of the rated output currentInverted L voltage drop, Automatic reset
Overvoltage protection Operated at 115 to 150 % of the rated output voltage, Shut-offResetting: Reset the power by turning it back (OFF time: at least 3 min)
Overheat protection No
Output voltage indication Yes (Resolution: 0.1 V / Accuracy: +/- 2% (percentage of output voltage value) +/- 1 digit Max.)
Output current indication Yes (Resolution: 0.1 A / Accuracy: +/- 5% F.S. (percentage of rated output current value) +/- 1 digit Max.)
Peak-hold current indication Yes (Resolution: 0.1 A / Accuracy: +/- 5% F.S. (percentage of rated output current value) +/- 1 digit Max. / Minimum detectable signal width: 10 ms (20 ms Max.))
Maintenance forecast monitor output No
Total run time monitor indication Yes (Resolution: 1 kh / Setting range: 1 to 150 kh)
Total run time monitor output Yes (open collector output), 30 VDC Max., 50 mA Max., Sinking (NPN)
Undervoltage alarm indication Yes (Resolution: 0.1 V / Setting range: 18.5 to 26.3 V)
Undervoltage alarm output Yes (open collector output), 30 VDC Max., 50 mA Max., Sinking (NPN)
Power failure alarm output No
Parallel operation No (However, backup operation is possible; external diodes required.)
Series operation Yes (Up to 2 Power Supplies with external diode)
Remote sensing function No
Applicable standard (UL) Standard No.: UL Listed: UL508 (Listing), UL UR: UL60950-1 (Recognition)
Applicable standard (CSA) Standard No.: cUL: CSA C22.2 No.107.1, cUR: CSA C22.2 No.60950-1
Applicable standard (EN) Standard No.: EN50178, EN60950-1
Applicable standard (EC Directive (EMI)) EMI: EN61204-3 Class BEmission Enclosure: Conforms to EN61204-3 Class AEmission AC mains: Conforms to EN61204-3 Class A and based on FCC Class AEMS: EN61204-3 High severity levels
Applicable standard(VDE) Standard No.: VDE0160, VDE0805 Teil 1 File number:
Applicable standard(SEMI) F47-0200 (200 VAC input)
Ambient temperature Operating: -10 to 60 CELStorage: -25 to 65 CEL(with no icing or condensation)
Ambient humidity Operating: 25 to 85%Storage: 25 to 90%(With no icing or condensation)
Dielectric strength Between all inputs and all outputs/alarm outputs: 3 kVAC for 1 min (Detection current: 20 mA)Between all inputs and PE terminals: 2 kVAC for 1 min (Detection current: 20 mA)Between all outputs/alarm outputs and all PE terminals: 1 kVAC for 1 min (Detection current: 20 mA)Between all outputs and all alarm outputs: 500 VAC for 1 min (Detection current: 20 mA)
Insulation resistance Between all outputs/alarm outputs and all inputs/PE terminals: 100 MOhm Min. (at 500 VDC)
Vibration resistance 10 to 55 Hz, 0.375 mm single amplitude in each 3 directions for 2 hours
Shock resistance 150 m/s**2, in each 6 directions 3 times
Output indicator Yes (color: green)
Heat radiation Natural air-cooling
Construction Covered type
Terminal type Screw terminal
Mounting type DIN Rail mounting type
Weight 1700 g Max.

Omron S8JX Switch Mode Power S8JX-G05005C
Omron S8JX Switch Mode Power S8JX-G05005C
Covered type , Input 100 to 240 VAC , 50 W , Output 5 V 10 A , Front-mounting typePower rating 50 WEfficiency 76% Min.Rated input voltage 100 to 240 VACAllowable-inp
Omron Power Supply S8VM Series S8VM-03024CD
Omron Power Supply S8VM Series S8VM-03024CD
Standard Type , Covered Type , DIN Rail Mounting Bracket Type , Input 100 to 240 VAC , 30 W , Output 24 V 1.3 APower rating 30 WEfficiency 81% Min.Rated in
Omron Power Supply S8VS Series S8VS-12024A
Omron Power Supply S8VS Series S8VS-12024A
Total Run Time Monitor , Input 100 to 240 VAC , 60 W , Output 24 V 2.5 APower rating 60 WEfficiency 83% TYP. ï¼ˆAt 100 VAC input)85% TYP. ï¼ˆAt 200 V
Omron S8JX Switch Mode Power S8JX-G03524D
Omron S8JX Switch Mode Power S8JX-G03524D
Open-Frame Type , Input 100 to 240 VAC , 35W , Output 24V 1.5A , DIN Rail mounting typePower rating 35 WEfficiency 73% Min.Rated input voltage 100 to 240 VACAllowable-inp
Omron Power Supply S8EX Series S8EX-N01512L
Omron Power Supply S8EX Series S8EX-N01512L
With chassis , Input 100 to 240 VAC , 15W , Output 12V 1.3APower rating 15 WEfficiency 77% Min. ï¼ˆAt 100 VAC input)77% Min. ï¼ˆAt 200 VAC input)Rated i
Omron Power Supply S8JX Switch Mode Power S8JX-P15048CD
Omron Power Supply S8JX Switch Mode Power S8JX-P15048CD
Covered type , Input 100 to 240 VAC , 150W , Output 48V 3.3A , DIN Rail mounting typePower rating 150 WEfficiency 82% Min.Rated input voltage 100 to 240 VACAllowable-inpu
Omron Power Supply S8JX Switch Mode Power S8JX-P30024CD
Omron Power Supply S8JX Switch Mode Power S8JX-P30024CD
Covered type , Input 100 to 240 VAC , 300W , Output 24V 14A , DIN Rail mounting typePower rating 300 WEfficiency 79% Min.Rated input voltage 100 to 240 VACAllowable-input
Omron S8JX Switch Mode Power S8JX-G01524C
Omron S8JX Switch Mode Power S8JX-G01524C
Covered type , Input 100 to 240 VAC , 15 W , Output 24 V 0.65 A , Front-mounting typeAs of November 15, 2012Power rating 15 WEfficiency 68% Min.Rated input volt
Omron Power Supply S8VM Series S8VM-10005C
Omron Power Supply S8VM Series S8VM-10005C
Standard Type , Covered Type , Bottom Mounting Type , Input 100 to 240 VAC , 100 W , Output 5 V 20 APower rating 100 WEfficiency 81% Min.Rated input voltage 100
Omron Power Supply S8EX Series S8EX-BP10048LC
Omron Power Supply S8EX Series S8EX-BP10048LC
With chassis and cover , Input 100 to 240 VAC , 100W , Output 48V 2.1APower rating 100 WEfficiency 84% Min. ï¼ˆAt 100 VAC input)86% Min. ï¼ˆAt 200 VAC in