Covered type , Input 100 to 240 VAC , 15 W , Output 12 V 1.3 A , Front-mounting type

As of November 15, 2012

Power rating 15 W
Efficiency 68% Min.
Rated input voltage 100 to 240 VAC
Allowable-input voltage variable range 85 to 264 VAC
80 to 370 VDC
Note at DC input The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Frequency 50/60 Hz (47 to 450 Hz Single-phase)
Rated input current 0.4 A Max. ï¼ˆAt 100 VAC input)
0.25 A Max. ï¼ˆAt 200 VAC input)
Leakage current 0.5 mA Max. (At 100 VAC input)
1 mA Max. (At 200 VAC input)
Inrush current 20 A Max. ï¼ˆAt 100 VAC input (For cold start at 25 CEL))
40 A Max. ï¼ˆAt 200 VAC input (For cold start at 25 CEL))
Rated output voltage 12 VDC
Output voltage variable range -10 to +15% (With V. ADJ)
(If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than the allowable voltage range. When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that load is not damaged.)
Ripple 2%(p-p) Max. (Under the rated I/O conditions.)
Static input variation influence 0.4% Max. (with AC input voltage)
Static load variation influence 0.8% Max. (At rated input, 0 to 100% load)
Ambient temperature variation influence 0.05 %/CEL Max. (At rated input/output voltage)
Rated output current 1.3 A
Start up time 500 ms Max. ï¼ˆUp to 90% of output voltage at rated input and output)
Hold time 20 ms Min. (At rated input voltage: 100 or 200 VAC at 100% load.)
Overload protection 105% to 175% of the rated output current
Voltage drop, Intermittent operation, Automatic reset
Overvoltage protection Operated at 120 to 140 % of the rated output voltage, Shut-off
Resetting: Reset the power by turning it back (OFF time: at least 7 min)
Overheat protection No
Maintenance forecast monitor output No
Total run time monitor output No
Undervoltage alarm output No
Power failure alarm output No
Parallel operation No (However, backup operation is possible; external diodes required.)
Series operation Yes (Up to 2 Power Supplies with external diode)
Remote sensing function No
Applicable standard (UL) Standard No.: UL Listed: UL508 (Listing), UL UR: UL60950-1 (Recognition)
Applicable standard (CSA) Standard No.: cUL Listed: CSA C22.2 No.107.1, cUR: CSA C22.2 No.60950-1
Applicable standard (EN) Standard No.: EN50178, EN60950-1
Applicable standard (EC Directive (EMI)) Emission Enclosure: Conforms to EN55011 Group 1 Class A
Emission AC mains: Conforms to EN55011 Group 1 Class A and based on FCC Class A
EMS: EN61204-3 High severity levels
Applicable standard(VDE) Standard No.: VDE0160, VDE0805 Teil 1 File number:
Applicable standard(SEMI) F47-0200 (200 VAC input)
Applicable standard(Other) Conformed standard 2: Terminal block: Based on DIN EN50274 (VDE0660-514)
Ambient temperature Operating: -10 to 60 CEL
Storage: -25 to 65 CEL
(with no icing or condensation)
Ambient humidity Operating: 25 to 85%
Storage: 25 to 90%
(With no icing or condensation)
Dielectric strength Between all inputs and all outputs: 3 kVAC for 1 min (Detection current: 20 mA)
Between all inputs and PE terminals: 2 kVAC for 1 min (Detection current: 20 mA)
Between all outputs and PE terminals: 1 kVAC for 1 min (Detection current: 20 mA)
Insulation resistance Between all outputs and all inputs/ PE terminals: 100 MOhm Min. (at 500 VDC)
Vibration resistance 10 to 55 Hz, 0.375 mm single amplitude in each 3 directions for 2 hours
Shock resistance 150 m/s**2, in each 6 directions 3 times
Output indicator Yes (color: green)
Heat radiation Natural air-cooling
Construction Covered type
Terminal type Screw terminal
Mounting type Front-mounting type
Bottom-mounting type
Side-mounting type
Attachment Front-mounting Bracket
Weight 270 g Max.

Omron Power Supply S8VS Series S8VS-24024BE-F
Omron Power Supply S8VS Series S8VS-24024BE-F
TotalPower rating 240 WEfficiency 85% TYP. ï¼ˆAt 100 VAC input)88% TYP. ï¼ˆAt 200 VAC input)Rated input voltage 100 to 240 VACAllowable-input voltage variable range 85 to 264 VAC8
Omron Power Supply S8VS Series S8VS-12024BP-F
Omron Power Supply S8VS Series S8VS-12024BP-F
Standard Model , Input 100 to 240 VAC , 15 W , Output 5 V 2 APower rating 15 WEfficiency 74% TYP. ï¼ˆAt 100 VAC input)73% TYP. ï¼ˆAt 200 VAC input)Rated&n
Omron Power Supply S8EX Series S8EX-P10005LC
Omron Power Supply S8EX Series S8EX-P10005LC
With chassis and cover , Input 100 to 240 VAC , 100W , Output 5V 20APower rating 100 WEfficiency 81% Min. ï¼ˆAt 100 VAC input)84% Min. ï¼ˆAt 200 VAC inpu
Omron Power Supply S82S S82S-7712
Omron Power Supply S82S S82S-7712
Input 12 to 24 VDC , 7.5 W , Output 12 V 0.6 APower rating 7.5 WEfficiency 69% Min.Rated input voltage 12 to 24 VDCAllowable-input voltage variable range 10.2 to 27.6&nbs
Omron Power Supply S8JX Switch Mode Power S8JX-P30024CD
Omron Power Supply S8JX Switch Mode Power S8JX-P30024CD
Covered type , Input 100 to 240 VAC , 300W , Output 24V 14A , DIN Rail mounting typePower rating 300 WEfficiency 79% Min.Rated input voltage 100 to 240 VACAllowable-input
Omron Power Supply S8VM Series S8VM-01524C
Omron Power Supply S8VM Series S8VM-01524C
Standard Type , Covered Type , Bottom Mounting Type , Input 100 to 240 VAC , 15 W , Output 24 V 0.65 APower rating 15 WEfficiency 80% Min.Rated input voltage 10
Omron Power Supply S8VS Series S8VS-09024BES
Omron Power Supply S8VS Series S8VS-09024BES
Total Run Time Monitor , Input 100 to 240 VAC , 90 W , Output 24 V 3.75 APower rating 90 WEfficiency 83% TYP. ï¼ˆAt 100 VAC input)85% TYP. ï¼ˆAt 200 
Omron S8JX Switch Mode Power S8JX-G60024C
Omron S8JX Switch Mode Power S8JX-G60024C
Covered type , Input 100/200 VAC , 100 W , Output 24 V 27 A , Front-mounting type Power rating 600 W Efficiency 80% Min. Rated input voltage 100 to 120 VAC200 to 
Omron Power Supply S8VS Series S8VS-09024BP-F
Omron Power Supply S8VS Series S8VS-09024BP-F
Maintenance Forecast Monitor Type , Input 100 to 240 VAC , 90 W , Output 24 V 3.75 A , With Undervoltage Alarm (Ttransistor (Sourcing))Power rating 90 WEfficiency 83%&nbs
Omron Power Supply S8VM Series S8VM-01515CD
Omron Power Supply S8VM Series S8VM-01515CD
Standard Type , Covered Type , DIN Rail Mounting Bracket Type , Input 100 to 240 VAC , 15 W , Output 15 V 1 APower rating 15 WEfficiency 78% Min.Rated inpu