Technical Specifications:
ELECTRICAL INPUT
Voltage 120 and 230 VAC nominal;
Online Voltage -30%, +20% for nominal voltages; user-selectable
Range extended range of -35%, +20% (-30%, +15% for 127
and 240 VAC)
Nominal Input 50/60 Hz; auto-selection (60 Hz only for 120 and 127 Vac)
Frequency
Frequency Tolerance Nominal ±3 Hz
ELECTRICAL OUTPUT
Power Levels 1000 – 3000 VA
Online Regulation -10%, +6%; within Computer Business Equipment
Manufacturers Association's Guidelines (-15%;
+10% using extended range)
On Battery Regulation <±5% RMS
Voltage Wave Shape Sine wave, 3% THD

Powerware 9 Prestige UPS Model 2500VA/1750W
Powerware 9 Prestige UPS Model 2500VA/1750W
Descriptions: The Powerware 9 Prestige is a versatile uninterruptible power system (UPS) designed to protect mission-critical applications such as hospitals, server farms, internet service providers, and manufacturing facilities. As a Series 9 UPS, the Prestige offers unparalle
Powerware 9125 UPS PW9125 3000G HW
Powerware 9125 UPS PW9125 3000G HW
Descriptions:the Powerware 9125 UPS delivers the ultimate in protection,truly isolating your equipment from all nine of the commonpower anomalies lurking in public utility power. Availableas either a rackmount or stand-alone unit, the compactand elegant 9125 supplies continuous, conditioned powerto
Powerware Plus18 UPS Model 15
Powerware Plus18 UPS Model 15
Specifications: Input Frequency Range 45-65 Hz Power Factor 0.95 Typical at full load Output Voltage Regulation Better than +/- 3% Voltage THD Less than 5% (100% nonlinear load); Less than 3% (100% linear load)Transient Response Less than 5% for 100% load, step full recovery within 1/4 cycl
Powerware 9125 UPS PW9125 700i
Powerware 9125 UPS PW9125 700i
Descriptions:the Powerware 9125 UPS delivers the ultimate in protection,truly isolating your equipment from all nine of the commonpower anomalies lurking in public utility power. Availableas either a rackmount or stand-alone unit, the compactand elegant 9125 supplies continuous, conditioned powerto
Powerware 9 Prestige UPS Model 750VA/525W EXT
Powerware 9 Prestige UPS Model 750VA/525W EXT
Specifications: Rating: 650-6000 VA Input Voltage: 120 Vac; 200–240 Vac Output Voltage: 120 Vac; 120/208 120/240 Vac Frequency: 50/60 Hz Configuration: Modular; rack-mount and cabinet
Powerware BPIII Industrial UPS 30-160 KVA
Powerware BPIII Industrial UPS 30-160 KVA
Specifications:Configuration 3-phase, 3-wire plus groundRange Nominal +10%, -15%Frequency range Nominal ±3 Hz (60 Hz)Power factor Minimum 0.9with filterPower walk-in 3 to 60 seconds to full loadInput current 10% THD under nominal conditionsdistortion with filterTransient protection 6 kV OC, 3 kA pe
Powerware 9305 UPS PW9305-7.5I-N
Powerware 9305 UPS PW9305-7.5I-N
Specifications:Rating 7.5 kVA Capacity (VA/Watts) 7.5 / 5.25 Dimensions WxDxH (mm) 400x750x700 Weight (kg) 180 Input connection Hardwired Output connection HardwiredTypical runtime (Full load) 18 min (Half load) 40 min
Powerware 9305 UPS PW9305-30I-N
Powerware 9305 UPS PW9305-30I-N
Specifications:Rating 30 kVA Capacity (VA/Watts) 30 kVA/21 kW Dimensions WxDxH (mm) 520x788x1530Weight (kg) 490Input connection Hardwired Output connection HardwiredTypical runtime (Full load) 7 min (Half load) 18 min
Powerware BPIV Industrial UPS 15 kVA/13.5 kw
Powerware BPIV Industrial UPS 15 kVA/13.5 kw
Descriptions:The BPIV delivers enhanced backup power, power quality, and system reliability with the highest efficiency ratings of any online UPS in the 10-30 kVA range for industrial equipment. Powerware Industrial UPS systems offer cost savings with the best power protection.
Powerware BPIII HE UPS 50 kVA/40 kw
Powerware BPIII HE UPS 50 kVA/40 kw
Specifications:Configuration: 3-Phase, 3 wire plus groundRange Nominal +10%, –15%Frequency range Nominal ±3 Hz (60 Hz)Power factor Minimum 0.9 with filterPower walk-in 3-60 seconds to full loadInput current 10% THD under nominal conditions distortion with filterTransient protection 6kV OC, 3 kV S