Specifications:
INPUT
Rated power 5000 VA
Voltage 220-230-240 Vac
Frequency 50/60 Hz ± 5 Hz
Power factor >0.98
Current distorsion ≤5%
BY PASS
Voltage tolerance 180÷264 Vac (selectable in Economy Mode and SMART ACTIVE Mode)
Frequency tolerance Selected frequency ± 5% (user configurable)
OUTPUT and INVERTER OUTPUT
Rated power 5000 VA
Active power 3500 W
Number phases 1
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Frequency 50/60 Hz selectable
Voltage distortion with distorcing load <5%
Voltage distortion with linear load <3%

Riello Multi Guard Industrial UPS GMI 160
Riello Multi Guard Industrial UPS GMI 160
Specifications:INPUTFrequency tolerance between 40 Hz and 72 HzPower factor >0.99BY PASSRated voltage 220-230-240 Vac, single-phase + NOUTPUT and INVERTER OUTPUTRated power 20000 VAActive power 18000 WFrequency 50 Hz / 60 HzENVIRONMENTALNoise from ≤ 52 dBA to ≤ 70 dBADATADimensions (h w d) 745 x
Riello Master HP UL UPS MHT UL 160
Riello Master HP UL UPS MHT UL 160
Specifications: Input voltage and frequency 480 VAC Three phase - 45~65 Hz ±2% selectable from ±1% to ±5% from front panel Output voltage ans frequency 380, 400, 415 VAC Three phase - 50/60 Hz (selactable Waveform Sinusoidal Power(KVA/KW)160/144 %Input voltage distoration (THDi) <3 Outpu
Riello Master MPS UPS MPM 20
Riello Master MPS UPS MPM 20
Specifications:INPUTVoltage 380 - 400 - 415 Vac three-phase VacFrequency 45 - 65 HzFrequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)Soft start 0 - 100% in 120’’ (selectable)Voltage Range 400 V + 20% /- 25%BY PASSRated voltage 360-400-420 Vac three-phase + NRated frequen
Rielloi Dialog Rack UPS IDR 1200
Rielloi Dialog Rack UPS IDR 1200
Specifications:INPUTRated power 1200 VAVoltage 220-240 VacVoltage tolerance 230 Vac (+ 20 / - 25%)Frequency 50/60 Hz auto sensingOUTPUT and INVERTER OUTPUTRated power 1200 VAActive power 720 WNumber phases 1Wave form on battery Pseudo sinewaveFrequency on battery operation 50 or 60 Hz (± 1%)BATTERI
Riello Master MPS UPS MPT 800
Riello Master MPS UPS MPT 800
Specifications: INPUT Voltage 380 - 400 - 415 Vac three-phase Vac Frequency 45 - 65 Hz Frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel) Soft start 0 - 100% in 120’’ (selectable) Voltage Range 400 V + 20% /- 25% BY PASS Rated voltage 380 - 400 - 415 Vac three-ph
Riello iPlug UPS IPG 800
Riello iPlug UPS IPG 800
Specifications:INPUTRated power 800 VAVoltage 220-240 VacVoltage tolerance 230 Vac (+ 20 / - 25%)Frequency 50/60 Hz with auto sensingOUTPUT and INVERTER OUTPUTRated power 800 VAActive power 480 WNumber phases 1Wave form on battery Pseudo sinewaveFrequency on battery operation 50 or 60 Hz (+/- 1%)BAT
Riello Dialog Vision UPS DVR 800
Riello Dialog Vision UPS DVR 800
Specifications: INPUT Rated power 800 VA Voltage 230 Vac Frequency 50/60 Hz with autorange Frequency tolerance ± 10Hz OUTPUT and INVERTER OUTPUT Rated power 800 VA Active power 540 W Number phases 1 Waveform Sinewave Frequency 50 or 60 Hz with autorange BATTERIES Type Maintenance-free
Riello Master Industrial UPS MIM 80
Riello Master Industrial UPS MIM 80
Specifications: INPUT Rated power 80000 VA Voltage 400 Vac three-phase Vac Voltage tolerance ± 20% Frequency 50/60 Hz with autorange Frequency tolerance 45/65 Hz Power factor 0.93 Current distorsion <5% Soft start 0-100% in 10" BY PASS Rated voltage 400 Vac three-phase selectable 380
Riello Master HE UPS MHE 250
Riello Master HE UPS MHE 250
Specifications: INPUT Rated power 250000 VA Voltage 400 Vac three-phase Vac Voltage tolerance + 20% - 25% Frequency 50/60 Hz with autorange Frequency tolerance 45/65 Hz Power factor 0,99 Input current 352 A Current distorsion <3% Soft start 0-100% in 10 BY PASS Rated voltage 400 Vac t