Home / Products / UPS Power Supply / APC UPS Power Supply / APC MGE EPS 8000 UPS / APC MGE EPS 8000 UPS E8TUPS750

APC MGE EPS 8000 UPS E8TUPS750

APC MGE EPS 8000 UPS E8TUPS750
share

Specifications:
General
Bypass Connection 4 wire (3Ph + N) or 5 wire (3Ph + N + G)
Bypass Voltage Tolerance +/-10% settable from +/-4/6/8 and 10%
Max Bypass Input Current 1140A
Output
Output Power Capacity 675 kW / 750 kVA
Max Configurable Power 675 kW / 750 kVA
Nominal Output Voltage 480V 3PH, 600V 3PH
Efficiency at Full Load 93.5%
Output Voltage Distortion Less than 2%
Output Frequency (sync to mains) 60 Hz
Other Output Voltages 600
Crest Factor 3.5 : 1
Topology Double Conversion Online
Waveform Type Sine wave
Output Connections
(1) Hard Wire 5-wire (3PH + N + G)
Output Voltage Tolerance +/- 0.5% static and +/- 2.5% 100% load step
Overload Operation 10 minutes @ 125% and 60 seconds @ 150%
Efficiency at Half Load 93.0%
Bypass Built-in Maintenance Bypass, External Manual Bypass
Input
Nominal Input Voltage 480V 3PH, 600V 3PH
Input Frequency 60 Hz
Input Connections
Hard Wire 4-wire (3PH + G)
Input voltage range for main operations 408 - 552 (480)V
Other Input Voltages 380, 400, 415, 600
Maximum Input Current 1043A
Input Total Harmonic Distortion Less than 7% for full load
Type of Input Protection Required 3-pole breaker

APC Symmetra PX UPS SY96K160H-NB
APC Symmetra PX UPS SY96K160H-NB
Specifications:GeneralBypass Connection 5 wire (3PH + N + G)Max Bypass Input Current 250ABypass Protection Device 250AOutputOutput Power Capacity 96 kW / 96 kVAMax Configurable Power 160 kW / 160 kVANominal Output Voltage 230V, 400V 3PHOutput Voltage Note Configurable for 380 : 400 or 415 V 3 Phase
APC MGE Galaxy 4000 UPS G4TUPS50
APC MGE Galaxy 4000 UPS G4TUPS50
Specifications: General Bypass Connection 5 wire (3PH + N + G) Bypass Voltage Tolerance +/- 15% Max Bypass Input Current 139A Output Output Power Capacity 40 kW / 50 kVA Max Configurable Power 40 kW / 50 kVA Nominal Output Voltage 208V 3PH Efficiency at Full Load 89.0% Output Voltage Disto
APC Symmetra PX UPS SY100K250DR-PD
APC Symmetra PX UPS SY100K250DR-PD
Specifications:GeneralBypass Voltage Tolerance +/-10% settable from +/-4/6/8 and 10%OutputOutput Power Capacity 100 kW / 100 kVAMax Configurable Power 500 kW / 500 kVANominal Output Voltage 400V 3PH, 480V 3PHOutput Voltage Distortion Less than 2%Output Frequency (sync to mains) 50 Hz, 60 HzOther Out
APC Smart-UPS VT SUVTP10KH4B4S
APC Smart-UPS VT SUVTP10KH4B4S
Specifications:OutputOutput Power Capacity 8000 Watts / 10 kVAMax Configurable Power 8000 Watts / 10 kVANominal Output Voltage 400V 3PHOutput Voltage Note Configurable for 380 : 400 or 415 V 3 Phase nominal output voltageEfficiency at Full Load 95.2%Output Voltage Distortion Less than 5% at full loa
APC MGE Galaxy 3500 UPS G35T20KF3B4S
APC MGE Galaxy 3500 UPS G35T20KF3B4S
Specifications:OutputOutput Power Capacity 16 kW / 20 kVAMax Configurable Power 16 kW / 20 kVANominal Output Voltage 208V 3PHOutput Voltage Note Configurable for 200 : 208 or 220V 3 Phase nominal output voltageEfficiency at Full Load 93.4%Output Voltage Distortion Less than 3%Output Frequency (sync
APC MGE Galaxy 5000 UPS G5TUPS40
APC MGE Galaxy 5000 UPS G5TUPS40
Specifications:OutputOutput Power Capacity 36 kW / 40 kVAMax Configurable Power 36 kW / 40 kVANominal Output Voltage 400V 3PH, 480V 3PH, 600V 3PHOutput Voltage Note Configurable for 380 : 400 or 415 V 3 Phase nominal output voltageEfficiency at Full Load 91.1%Output Voltage Distortion Less than 2%Ou
APC Symmetra PX UPS SY150K250D
APC Symmetra PX UPS SY150K250D
Specifications:GeneralBypass Voltage Tolerance +/-10% settable from +/-4/6/8 and 10%OutputOutput Power Capacity 150 kW / 150 kVAMax Configurable Power 500 kW / 500 kVANominal Output Voltage 400V 3PH, 480V 3PHOutput Voltage Distortion Less than 2%Output Frequency (sync to mains) 50 Hz, 60 HzOther Out
APC Galaxy VM UPS GVMPB225KGS
APC Galaxy VM UPS GVMPB225KGS
Specifications:GeneralBypass Connection Built-in Static BypassBypass Voltage Tolerance +/-10% settable from +/-4/6/8 and 10%Max Bypass Input Current 350ABypass Protection Device 400AOutputOutput Power Capacity 202.5 kW / 225 kVAMax Configurable Power 202.5 kW / 225 kVANominal Output Voltage 480V 3PH
APC Smart-UPS VT SUVTP40KH4B4S
APC Smart-UPS VT SUVTP40KH4B4S
Specifications:OutputOutput Power Capacity 32 kW / 40 kVAMax Configurable Power 32 kW / 40 kVANominal Output Voltage 400V 3PHOutput Voltage Note Configurable for 380 : 400 or 415 V 3 Phase nominal output voltageEfficiency at Full Load 96.0%Output Voltage Distortion Less than 5% at full loadOutput Fr
APC Smart-UPS SURTD5000RMXLT3U
APC Smart-UPS SURTD5000RMXLT3U
Specifications:OutputOutput Power Capacity 3500 Watts / 5000 VAMax Configurable Power 3500 Watts / 5000 VANominal Output Voltage 208VOutput Voltage Note Configurable for 208 or 240 nominal output voltageEfficiency at Full Load 91.0%Output Voltage Distortion Less than 3%Output Frequency (sync to main