Cart()
 
 
Categories
Contact Us
  • A&S Power Supply Co.,Ltd
  • Address:469, Xinsheng Road, Gaoxin District, Chengdu, Sichuan, China
  • Tel:+86-28-65376776
  • Fax:+86-28-86129221
  • Email:inverter@electrical8.com
  • Contact Person:Karina
Home / Products / UPS Power Supply / APC UPS Power Supply / APC MGE Galaxy 5000 UPS / APC MGE Galaxy 5000 UPS G5TUPS80

APC MGE Galaxy 5000 UPS G5TUPS80

APC MGE Galaxy 5000 UPS G5TUPS80
share

Specifications:
Output
Output Power Capacity 72 kW / 80 kVA
Max Configurable Power 72 kW / 80 kVA
Nominal Output Voltage 400V 3PH, 480V 3PH, 600V 3PH
Output Voltage Note Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
Efficiency at Full Load 92.8%
Output Voltage Distortion Less than 2%
Output Frequency (sync to mains) 50 Hz - programmable +/- 0.5 / 1 / 2 / 4 / 6 / 8%
Other Output Voltages 380, 415
Crest Factor 3 : 1
Topology Double Conversion Online
Waveform Type Sine wave
Output Connections
(1) Hard Wire 4-wire (3PH + G)
(1) Hard Wire 5-wire (3PH + N + G)
Output Voltage Tolerance +/- 1% static and +/- 2 % at 100% load step
Output Voltage THD < 1% linear load and < 2.5% nonlinear load
Overload Operation 10 minutes @ 125% and 60 seconds @ 150%
Efficiency at Half Load 90.0%
Required Output Current Protection 115A
Bypass Internal Bypass (Automatic and Manual), Optional External Bypass
Input
Nominal Input Voltage 400V 3PH, 480V 3PH, 600V 3PH
Input Frequency 45 - 65 Hz
Input Connections
Hard Wire 4-wire (3PH + G)
Input voltage range for main operations 340 - 460 (400V), 408 - 538V
Other Input Voltages 380, 400, 415
Maximum Input Current 152A
Input Breaker Capacity 250 A
Maximum Short Circuit Withstand (Icw) 30.0 kA
Input Total Harmonic Distortion Less than 3% for full load
Type of Input Protection Required 3-pole breaker

APC Galaxy VM UPS GVMPB160KGS
APC Galaxy VM UPS GVMPB160KGS
Specifications:GeneralBypass Connection Built-in Static BypassBypass Voltage Tolerance +/-10% settable from +/-4/6/8 and 10%Max Bypass Input Current 217ABypass Protection Device 400AOutputOutput Power Capacity 144 kW / 160 kVAMax Configurable Power 144 kW / 160 kVANominal Output Voltage 480V 3PHOutp
APC MGE Galaxy 3500 UPS G35T15KHS
APC MGE Galaxy 3500 UPS G35T15KHS
Specifications:OutputOutput Power Capacity 12 kW / 15 kVAMax Configurable Power 12 kW / 15 kVANominal Output Voltage 400V 3PHOutput Voltage Note Configurable for 380 : 400 or 415 V 3 Phase nominal output voltageEfficiency at Full Load 95.8%Output Voltage Distortion Less than 5%Output Frequency (sync
APC Symmetra PX UPS SY64K160H-NB
APC Symmetra PX UPS SY64K160H-NB
Specifications:GeneralBypass Connection 5 wire (3PH + N + G)Max Bypass Input Current 250ABypass Protection Device 250AOutputOutput Power Capacity 64 kW / 64 kVAMax Configurable Power 160 kW / 160 kVANominal Output Voltage 230V, 400V 3PHOutput Voltage Note Configurable for 380 : 400 or 415 V 3 Phase
APC MGE Galaxy 3500 UPS G35T15KF4B4S
APC MGE Galaxy 3500 UPS G35T15KF4B4S
Specifications:OutputOutput Power Capacity 12 kW / 15 kVAMax Configurable Power 12 kW / 15 kVANominal Output Voltage 208V 3PHOutput Voltage Note Configurable for 200 : 208 or 220V 3 Phase nominal output voltageEfficiency at Full Load 93.0%Output Frequency (sync to mains) 57 - 63 Hz for 60 Hz nominal
APC Smart-UPS SURTA1000XL
APC Smart-UPS SURTA1000XL
Specifications:OutputOutput Power Capacity 800 Watts / 1000 VAMax Configurable Power 800 Watts / 1000 VANominal Output Voltage 120VOutput Voltage Distortion Less than 3%Output Frequency (sync to mains) 50/60 Hz +/- 3 Hz user adjustable +/- 0.1Crest Factor 3 : 1Topology Double Conversion OnlineWavefo
APC Galaxy VM UPS GVMSB160KGS
APC Galaxy VM UPS GVMSB160KGS
Specifications:GeneralBypass Connection Built-in Static BypassBypass Voltage Tolerance +/-10% settable from +/-4/6/8 and 10%Max Bypass Input Current 217ABypass Protection Device 400AOutputOutput Power Capacity 144 kW / 160 kVAMax Configurable Power 144 kW / 160 kVANominal Output Voltage 480V 3PHOutp
APC Back-UPS Connect BGE90M
APC Back-UPS Connect BGE90M
Specifications:OutputOutput Power Capacity 75 Watts / 125 VAMax Configurable Power 75 Watts / 125 VANominal Output Voltage 120VOutput Frequency (sync to mains) 50/60 Hz +/-1 HzWaveform Type Square waveOutput Connections(3) NEMA 1-15R (Battery Backup) InputNominal Input Voltage 120VInput Frequency 50
APC MGE Galaxy 3500 UPS G35TEFXFM10K40H
APC MGE Galaxy 3500 UPS G35TEFXFM10K40H
Specifications:OutputNominal Output Voltage 400V 3PHInputNominal Input Voltage 400V 3PHInput Frequency 50 HzPhysicalNet Weight 147.00 KGMaximum Height 1487.00 mmMaximum Width 523.00 mmMaximum Depth 837.00 mmShipping Weight 181.00 KGShipping Height 1663.00 mmShipping Width 723.00 mmShipping Depth 110
APC MGE Galaxy 3500 UPS G35T15KH2B2S
APC MGE Galaxy 3500 UPS G35T15KH2B2S
Specifications:OutputOutput Power Capacity 12 kW / 15 kVAMax Configurable Power 12 kW / 15 kVANominal Output Voltage 400V 3PHOutput Voltage Note Configurable for 380 : 400 or 415 V 3 Phase nominal output voltageEfficiency at Full Load 95.8%Output Voltage Distortion Less than 5%Output Frequency (sync
APC Back-UPS BX650CI-LM
APC Back-UPS BX650CI-LM
Back-UPS specification:Output Power Capacity 320 Watts / 575 VAMax Configurable Power 320 Watts / 575 VANominal Output Voltage 120VEfficiency at Full Load 70.0%Output Frequency (sync to mains) 50/60 Hz +/-1 HzTopology Line InteractiveWaveform Type Square waveOutput Connections(2) NEMA 5-15R (Surge P