Specifications:
Output
Output Power Capacity 90 kW / 100 kVA
Max Configurable Power 90 kW / 0 VA
Nominal Output Voltage 480V 3PH, 600V 3PH
Efficiency at Full Load 92.9%
Output Voltage Distortion Less than 2%
Output Frequency (sync to mains) 60 Hz
Crest Factor 3 : 1
Topology Double Conversion Online
Waveform Type Sine wave
Output Connections
(1) Hard Wire 4-wire (3PH + G)
(1) Hard Wire 5-wire (3PH + N + G)
Output Voltage Tolerance +/- 1% static and +/- 2 % at 100% load step
Output Voltage THD < 1% linear load and < 2.5% nonlinear load
Overload Operation 10 minutes @ 125% and 60 seconds @ 150%
Efficiency at Half Load 91.6%
Required Output Current Protection 144A
Neutral Output Current 217A
Bypass Internal Bypass (Automatic and Manual), Optional External Bypass
Input
Nominal Input Voltage 480V 3PH, 600V 3PH
Input Frequency 45 - 65 Hz
Input Connections
Hard Wire 4-wire (3PH + G)
Input voltage range for main operations 408 - 552 (480)V
Input voltage adjustable range for mains operation 408 - 552 (480V)V
Other Input Voltages 600
Maximum Input Current 190A
Input Breaker Capacity 250 A
Maximum Short Circuit Withstand (Icw) 30.0 kA
Input Total Harmonic Distortion Less than 3% for full load
Type of Input Protection Required 3-pole breaker

APC MGE Galaxy 4000 UPS G4TUPS75
APC MGE Galaxy 4000 UPS G4TUPS75
Specifications: General Bypass Connection 5 wire (3PH + N + G) Bypass Voltage Tolerance +/- 15% Max Bypass Input Current 208A Output Output Power Capacity 60 kW / 75 kVA Max Configurable Power 60 kW / 75 kVA Nominal Output Voltage 208V 3PH Efficiency at Full Load 87.4% Output Voltage Disto
APC Symmetra UPS SYH6K6RMT
APC Symmetra UPS SYH6K6RMT
Specifications:OutputOutput Power Capacity 4200 Watts / 6000 VAMax Configurable Power 4200 Watts / 6000 VANominal Output Voltage 208VOutput Voltage Note Configurable for 208 or 240 nominal output voltageEfficiency at Full Load 89.0%Output Voltage Distortion Less than 5% at full loadOutput Frequency
APC Smart-UPS SURTD5000XLT-1TF3
APC Smart-UPS SURTD5000XLT-1TF3
Specifications:OutputOutput Power Capacity 3500 Watts / 5000 VAMax Configurable Power 3500 Watts / 5000 VANominal Output Voltage 120V, 208VOutput Voltage Note Configurable for 208 or 240 nominal output voltageEfficiency at Full Load 91.0%Output Voltage Distortion Less than 3%Output Frequency (sync t
APC Smart-UPS VT SUVTR30KF4B5S
APC Smart-UPS VT SUVTR30KF4B5S
Specifications:OutputOutput Power Capacity 24 kW / 30 kVAMax Configurable Power 24 kW / 30 kVANominal Output Voltage 120V, 208V, 208V 3PHOutput Voltage Note Configurable for 200 : 208 or 220V 3 Phase nominal output voltageOutput Voltage Distortion Less than 5% at full loadOutput Frequency (sync to m
APC Symmetra PX UPS SY64K96H-NB
APC Symmetra PX UPS SY64K96H-NB
Specifications:GeneralBypass Connection 5 wire (3PH + N + G)Max Bypass Input Current 250ABypass Protection Device 250AOutputOutput Power Capacity 64 kW / 64 kVAMax Configurable Power 160 kW / 160 kVANominal Output Voltage 230V, 400V 3PHOutput Voltage Note Configurable for 380 : 400 or 415 V 3 Phase
APC MGE Galaxy 3500 UPS G35T15KHS
APC MGE Galaxy 3500 UPS G35T15KHS
Specifications:OutputOutput Power Capacity 12 kW / 15 kVAMax Configurable Power 12 kW / 15 kVANominal Output Voltage 400V 3PHOutput Voltage Note Configurable for 380 : 400 or 415 V 3 Phase nominal output voltageEfficiency at Full Load 95.8%Output Voltage Distortion Less than 5%Output Frequency (sync
APC MGE Galaxy 3500 UPS G35T10KHS
APC MGE Galaxy 3500 UPS G35T10KHS
Specifications:OutputOutput Power Capacity 8000 Watts / 10 kVAMax Configurable Power 8000 Watts / 10 kVANominal Output Voltage 400V 3PHOutput Voltage Note Configurable for 380 : 400 or 415 V 3 Phase nominal output voltageEfficiency at Full Load 94.5%Output Voltage Distortion Less than 5%Output Frequ
APC Smart-UPS VT SUVTP20KH4B4S
APC Smart-UPS VT SUVTP20KH4B4S
Specifications:OutputOutput Power Capacity 16 kW / 20 kVAMax Configurable Power 16 kW / 20 kVANominal Output Voltage 400V 3PHOutput Voltage Note Configurable for 380 : 400 or 415 V 3 Phase nominal output voltageEfficiency at Full Load 95.3%Output Voltage Distortion Less than 5% at full loadOutput Fr
APC Smart-UPS VT SUVTP30KH4B4S
APC Smart-UPS VT SUVTP30KH4B4S
Specifications:OutputOutput Power Capacity 24 kW / 30 kVAMax Configurable Power 24 kW / 30 kVANominal Output Voltage 400V 3PHOutput Voltage Note Configurable for 380 : 400 or 415 V 3 Phase nominal output voltageEfficiency at Full Load 96.4%Output Voltage Distortion Less than 5% at full loadOutput Fr
APC MGE Galaxy 3500 UPS G35TXFM10K30F
APC MGE Galaxy 3500 UPS G35TXFM10K30F